ov on DELTA inverters: DC bus over-voltage

DELTA inverters: VFD-EL

Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.

Common causes

  1. Deceleration too fast, the motor regenerates into the drive
  2. High-inertia or overhauling load (large fan, lowering hoist)
  3. Supply voltage above the allowed range

Try first

  1. Increase the deceleration time (Pr.01-10)
  2. Enable over-voltage stall prevention if available
  3. Measure the supply: 1-phase 230 V on 21A models
  4. If it repeats on heavy loads, add a suitable braking resisto