oL1
oL1 on DELTA inverters: Motor overload (electronic thermal)
DELTA inverters: VFD-EL
Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.
Common causes
- Motor current above the setting
- Wrong motor rated current in the parameters
- Long low-speed running of a self-cooled motor
Try first
- Set the motor rated current from the nameplate (Pr.07-00)
- Check the mechanical load and bearings
- Avoid long low-speed running without extra cooling