oL

oL

oL on DELTA inverters: Drive overload

DELTA inverters: VFD-EL، MS300

Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.

Common causes

  1. Load above the drive rating for too long
  2. Heavy, frequent acceleration
  3. Torque boost or V/f set too high

Try first

  1. Measure the running current and compare with the drive rating
  2. Increase the acceleration time
  3. Reduce the load or choose a larger drive
Not solved?Ask Electro for a technician or a larger inverter

Parts for this fault

All DELTA codes