ocA
ocA on DELTA inverters: Over-current during acceleration
DELTA inverters: MS300
Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.
Common causes
- Acceleration time too short
- Short in the motor cable or winding
- Torque boost set too high
- Drive too small for the load
Try first
- Increase the acceleration time (Pr.01-12)
- Test the drive without the motor, then megger the cable and motor
- Lower the torque boost
- For heavy-start loads choose a larger drive