ocA

ocA

ocA on DELTA inverters: Over-current during acceleration

DELTA inverters: MS300

Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.

Common causes

  1. Acceleration time too short
  2. Short in the motor cable or winding
  3. Torque boost set too high
  4. Drive too small for the load

Try first

  1. Increase the acceleration time (Pr.01-12)
  2. Test the drive without the motor, then megger the cable and motor
  3. Lower the torque boost
  4. For heavy-start loads choose a larger drive
Not solved?Ask Electro for a technician or a larger inverter