oc

oc

oc on DELTA inverters: Output over-current

DELTA inverters: VFD-EL

Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.

Common causes

  1. Short circuit in the motor cable or winding
  2. Acceleration or deceleration time too short
  3. Drive rating smaller than the motor or load
  4. Jammed or suddenly heavy mechanical load
  5. A contactor switching betwe

Try first

  1. Disconnect U, V, W and run the drive without the motor: if the fault clears, check the cable and motor
  2. Megger the motor and cable insulation
  3. Increase Pr.01-09 (accel) and Pr.01-10 (decel)
  4. Check the dr
Not solved?Ask Electro for a technician or a larger inverter