oc
oc on DELTA inverters: Output over-current
DELTA inverters: VFD-EL
Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.
Common causes
- Short circuit in the motor cable or winding
- Acceleration or deceleration time too short
- Drive rating smaller than the motor or load
- Jammed or suddenly heavy mechanical load
- A contactor switching betwe
Try first
- Disconnect U, V, W and run the drive without the motor: if the fault clears, check the cable and motor
- Megger the motor and cable insulation
- Increase Pr.01-09 (accel) and Pr.01-10 (decel)
- Check the dr