GFF on DELTA inverters: Ground fault

DELTA inverters: VFD-EL، MS300

Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.

Common causes

  1. Damaged insulation in the motor cable or winding
  2. Moisture in the motor terminal box
  3. Very long motor cable
  4. Internal drive damage

Try first

  1. Disconnect the motor and megger each phase to ground
  2. Dry the motor terminal box
  3. If the fault stays with no motor connected, the drive needs repair