CE10 on DELTA inverters: RS-485 communication time-out
DELTA inverters: VFD-EL، MS300
Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.
Common causes
- No message from the PLC or HMI within the set time
- Broken or reversed communication wire
- Baud rate or address mismatch
Try first
- Check the RS-485 wire, +/- and ground
- Match baud rate, address and format with the PLC (group 09)
- Review the time-out setting (Pr.09-03)