ACE
ACE on DELTA inverters: ACI signal loss
DELTA inverters: MS300
Disconnect the supply and wait for the capacitors to discharge before opening the inverter or touching its terminals.
Common causes
- Broken 4-20 mA signal wire
- Sensor damaged or unpowered
Try first
- Measure the signal at the ACI terminal
- Check the sensor and its supply
- Review the loss-of-signal action (Pr.03-19)